Protocol : VA TECH SAT - SAT1703 ( External data block format standard )


 

Parameterization :

CDE adapter :

Modulations mode :

Transmission rates :

Data byte :

Stop bit :

Parity :

Time out :

Hamming distance :

Station number :

switch setting  PCM

pulse-code-modulation asynchronous

300 - 57600 baud

8 bit  ( variable )

1 bit ( variable )

even ( variable )

250 msec ( variable )

4

yes / no

Telegram structure :

The protocol SAT1703 uses only the format class FT 1.2, corresponding to the IEC standard TC57 Part 5.1.  (Transmission Frame Formats). Frames with fixed and variable length are also permissible as single signs A2H and E5H.  The transmission of data bytes takes place after the principle "LSB first".

It is an asynchronous protocol with the hamming distance = 4. The sequence of the user data is closed by an 8-bit check sum. The check sum is the arithmetic sum of all user data octets.

 

Telegram format : Packed

Packed telegram with variable length :

 

Status
I / NEZ / A
S
G
H / NS
T
Invalid / not real time correct / interrogation
spontaneous
General interrogation
high prior / Not able to classify
Test value

 

Packed telegram with fixed length :

 

Telegram format : Unpacked

Unpacked telegram with variable length :

 

Status
I / NEZ / A
S
G
H / NS
T
Invalid / not real time correct / interrogation
spontaneous
General interrogation
high prior / Not able to classify
Test value

 

Unpacked telegram with fixed length :

Header
B0
B1
Q0
Q1
R
T
UE
D
Buffer 0
Buffer 1
Acknowledge for Buffer 0 
Acknowledge for Buffer 1
Retry bit for identification of telegram repetitions
Telegram number bit
Transfer bit
Dummy ( not used , always 0 )

 

Telegram format : With address- and specified function field

Unpacked telegram with variable length and station number :

 

 

Status
I / NEZ / A
S
G
H
NS
T
Invalid / Not real time correct / Query 
Spontaneous
General interrogation
High priory
Not able to classify
Test value

Unpacked telegram with fixed length and station number :

 

Address field
M Master bit :
1 = Master to telecontrol station ( M -> S )
0 = Telecontrol station to  master ( S -> M )

 

Function field
R
D
C / S

Q
TR
TT
IN M / S

A / E
Reserve
S -> M : Acknowledge bit for data telegram to all  
M -> S : Clear Bit (not used)
S -> M : Acknowledge bit for system telegram to all 
Acknowledge bit for data telegram
Expected telegram number in receive-direction ( data telegram )
Telegram number in transmit-direction ( data telegram )
M -> S : Initialization request for Slave, telegram number in receive-direction
S -> M : Acknowledge for the receipt of the global initialization request.( A2H )
M -> S : Call bit
S -> M : End bit ( no more data are to be sent )

 

Single sign :

A2H : Master -> Slave

Reset of remote link
Initialization of all telegram numbers in transmit- and receive direction as well as deletion of all acknowledge bits. The receipt of the single sign A2H is is confirmed by the N-S bit in the opposite direction. 

E5H : Slave -> Master

Positive Acknowledge without indicating the telecontrol stration. 
End telegram after call if no data are available and no acknowledges  (e.g. telegram to all) are to be transmitted. 

 

Simulation mode

 

RTI (Master)-Simulation

 

Station initialization

When starting the RTI-simulation all telegram numbers in receive- and transmit direction in LIAN DOS are initialized. The multiple transmission ( 3 times ) of the single sign A2H as request for the initialization forces the substation to initialize all telegram numbers in transmit- and receive direction, too.

 

RTU (Slave)-Simulation

 

Transmission errors

*F:BCCode : The Telegram check sum is not correct.
*F:Block length : The stop byte is missing or is not on the right place.
*F:TelFormat : The telegram header of the 68H telegram is faulty.
*F:SYNC :

The receive routine searches for  68H or 10H. Every other character is given an asterisk '*' in SIMO and a synchronization error is noted against it in the protocol.

*F:Overflow : Error message from the UART.
*F:Parity : Error message from the UART.
*F:Start/Stop : Error message from the UART.

 


MAYR Software