Protocol : Siemens - SINAUT 8-FW ( PDM )


 

Parameterization :

CDE adapter :

Modulation mode :

Transmission rates :

Hamming distance s /e :

Tolerance limit :

Message gap :

Station number yes / no :

Direction :
  

Traffic mode PtP / MuP :
  
    

PC-TxT level :

switch setting  PDM

Digital-pulse-duration-modulation

50 - 2400 baud

4 / 4  ( variable )

0 - 50% 

6.6 ( variable )

Transmission with or without station number and TGE-bit.

For a correct interpretation of a short messages the control or monitoring direction should be set.

PtP ( Point to Point ) / MuP ( Multi Point ) : 
The switch-on pulse is filtered out when receiving. The simulation mode in SIMO is affected by MuP.

-12V / +12V

Particular features with the parameterization

The station-number, always existing with MuP, can be set differently for transmitting and receiving with PtP. In control direction a station number is always expected in the telegram.

Possible settings :
The station-number can be included only in control direction or in both directions.

The direction for the receipt must be declared additional if the station-number is only set in control direction.

Telegram structure

Information types 

With certain protocols, it is not possible to distinguish the various message-types. Therefore a protocol specific list is introduced to the type identification. This list describes the allocation of the message address to the message-type.

A created list can be saved over < File | load | INFTYP > when required. If the < Configuration window > displays in the line Information type "?????" the list is faulty or not created.

Sinaut 8-FW telegram types   control direction :
type 64 = TDB_S8FW_SB1
type 65 = TDB_S8FW_SB2 
type 66 = TDB_S8FW_SB3
type 67 = TDB_S8FW_SB4
type 68 = TDB_S8FW_SB5
type 69 = TDB_S8FW_SB6
type 70 = TDB_S8FW_SB7
control
analogue set point , 1 MV 8 bit
analogue set point , 4 MV 8 bit
analogue set point , 8 MV 8 bit
digital set point , 8 bit
digital set point , 16 bit
digital set point , 32 bit
      organizational :
type 192 = TDB_S8FW_SO1
type 193 = TDB_S8FW_SO2
type 194 = TDB_S8FW_SO3
type 195 = TDB_S8FW_SO4
type 196 = TDB_S8FW_SO5
type 197 = TDB_S8FW_SO6
type 198 = TDB_S8FW_SO7
type 199 = TDB_S8FW_SO8
type 200 = TDB_S8FW_SO9 
type 201 = TDB_S8FW_SO10
type 202 = TDB_S8FW_SO11
type 203 = TDB_S8FW_SO12
type 204 = TDB_S8FW_SO13
type 205 = TDB_S8FW_SO14
type 206 = TDB_S8FW_SO15
type 207 = TDB_S8FW_SO16
type 208 = TDB_S8FW_SO17
type 209 = TDB_S8FW_SO18
type 210 = TDB_S8FW_SO19
type 211 = TDB_S8FW_SO20
type 212 = TDB_S8FW_SO21
type 213 = TDB_S8FW_SO22 
type 214 = TDB_S8FW_SO23 
type 215 = TDB_S8FW_SO24 
type 216 = TDB_S8FW_SO25 
type 217 = TDB_S8FW_SO26 
type 218 = TDB_S8FW_SO27 
type 219 = TDB_S8FW_SO28 
type 220 = TDB_S8FW_SO29 
type 221 = TDB_S8FW_SO30 
type 222 = TDB_S8FW_SO31 
check command
message repeat request / TFK-acknowledge
start acknowledgement
replace command 
single interrogation command 
group interrogation command
multiple request on ( terminated )
multiple request on ( not terminated )
multiple request switch off
switch on for temporal lists
switch off for temporal lists
switch on / off recipient in master station
switch off record transfer from / to station
modification of threshold value limit
modification of smoothing factor
synchronization of fine time 
setting of minutes
setting of calendar
switch on / off addresses in the lists
start-up request ( start up / restart )
remote parameterization
matrix-check command ( receipt on "1" )
4-byte-storage interrogation control
interrogation command ZFBIT and STOP-cause
project specific reserved with FW 512
project specific reserved with FW 512
project specific reserved with FW 512
project specific reserved with FW 512
project specific reserved with FW 512
project specific reserved with FW 512
project specific reserved with FW 512
Sinaut 8-FW telegram types   monitoring direction :
type 00 = TDB_S8FW_UEB1
type 01 = TDB_S8FW_UEB2 
type 02 = TDB_S8FW_UEB3 
type 03 = TDB_S8FW_UEB4 
type 04 = TDB_S8FW_UEB5 
type 05 = TDB_S8FW_UEB6 
type 06 = TDB_S8FW_UEB7 
type 07 = TDB_S8FW_UEB8 
type 08 = TDB_S8FW_UEB9 
type 09 = TDB_S8FW_UEB10 
type 10 = TDB_S8FW_UEB11 
type 11 = TDB_S8FW_UEB12 
type 12 = TDB_S8FW_UEB13 
type 13 = TDB_S8FW_UEB14 
type 14 = TDB_S8FW_UEB15 
type 15 = TDB_S8FW_UEB16 
type 16 = TDB_S8FW_UEB17 
4 bitmap per 8 bit
1 bitmap per 32 bit
indication , 1 byte
indication , 4 byte
indication , 8 byte
indication , 1 byte time tagged
measurements , 1 MV 8 bit
measurements , 4 MV 8 bit
measurements , 8 MV 8 bit
measurements , 2 MV 11 bit
measurements , 4 MV 11 bit
Wischermeldungen 4 byte
Wischermeldungen time tagged
trafo tap 6 bit + run, 4 byte
counters BCD coded
counters dual coded
measurements , 4 MV time tagged
      organizational :
type 128 = TDB_S8FW_UEO1 
type 129 = TDB_S8FW_UEO2 
type 130 = TDB_S8FW_UEO3 
type 131 = TDB_S8FW_UEO4 
type 132 = TDB_S8FW_UEO5 
type 133 = TDB_S8FW_UEO6 
type 134 = TDB_S8FW_UEO7 
type 135 = TDB_S8FW_UEO8 
type 136 = TDB_S8FW_UEO9 
type 137 = TDB_S8FW_UEO10 
type 138 = TDB_S8FW_UEO11 
type 139 = TDB_S8FW_UEO12 
type 140 = TDB_S8FW_UEO13 
type 141 = TDB_S8FW_UEO14 
type 142 = TDB_S8FW_UEO15 
type 143 = TDB_S8FW_UEO16 
type 144 = TDB_S8FW_UEO17 
type 145 = TDB_S8FW_UEO18 
type 146 = TDB_S8FW_UEO19 
check command
single fault record substation
single fault record master station
acknowledge "check back before operate"
acknowledge "threshold operation"
acknowledge "smoothing factor operation"
acknowledge "synchronization"
acknowledge "setting minutes"
acknowledge "setting calendar"
acknowledge start-up request
neg. acknowl. "remote parameterization"
storage content transfer "4 Byte"
error bit pattern transfer "ZFBIT"
last stop-cause "ZX STOP"
error message of a disturbed substation
operating bit pattern
operating bit pattern of SINAUT8-FWA 1024
neg. acknowl. single -/ multiple request
acknowl. "multiple request stopped"

Simulation mode :

In SIMO you can simulate a master station or substation by the commands "rti" and "rtu".

Polling :
  
 rti [ station number ( 0 - 127 ) ] => simulate master station
rtu [ station number ( 0 - 127 ) ] => simulate substation 

The station number handed over as parameter is entered into each telegram. The MSC-number is set correctly. If needed SIMO sends back telegrams automatically with the following send buffers reserved (these buffers should not be occupied otherwise ):

Num Commentary STA T D Addr S Data hexadecimal
495
496
497
498
499
startUpInterrogation     495
TFK-ACK                   496
ZX STOP                    497
ZF Bit                        498
check command         499
1
0
1
1
1
0
0
0
0
0
0
0
0
0
514
513
782
781
512
0
0
0
0
0
00 00
00 00
00 00 00 00 00 00 00 00 00
00 00 00 00 00
AA 55

Especially for transmitting short messages the following commands are available :
qc
qs [ station number ]
an [ station number ]
nq [ station number ]
al1 - al4
transmit quick check
transmit quick scan
transmit indication
transmit negative acknowledgement
transmit interrogation list 1 - 4

Bit shifter

In SIMO you can activate a bit shifter via the command "bs". It enables you to set a bit conveniently into the information block of the relevant telegram. When exceeding the information area the message address is automatically increased or reduced.

In the window "bit shifter" you can use the following command :
[ 1-9 ] define interval n
[ arrow-right ] n bit to the right
[ arrow-left ] n bit to the left
[ arrow-up ] increase message address by 1
[ arrow-down ] reduce message address by 1
[ S ] send message
[ ESC ] quit entry mask

It should be taken into account that the bit shifter doesn't change the message address and the information block ; previous settings are not lost. Furthermore its application is not useful with all message types ( only indications and fleetings ). Short messages are not processed.

Filter-/Trigger-setting

Short-telegram ( StR / UeR ) :
0 = QuickCheck / Registration
1 = QuickScan / NegativAcknowledgement
2 = interrogation list 1
3 = interrogation list 2
4 = interrogation list 3
5 = interrogation list 4
6 = single query 1
7 = single query 2
8 = single query 3
9 = single query 4
Station-number : 0 - 127
MSC-bit : 0 / 1

Data mode :
0 = organizational
1 = spontaneous
2 = cyclic
3 = interrogated

Record-number : 0 - 1023
System-number : 0 - 7


Plain text display format

The output for each channel can be manipulated over the menu item <Format> in the programs SIMO, TRAP and TDEP. To optimise the output one can distinguish between three plain text settings for protocols with long telegrams.

Plain text F 1

Plain text F 2

Plain text F 3

the complete telegram (  identification + information ) is displayed

output of  data unit identifier ( no information )

output of the information only

 

Transmission errors

*F:Blocklength :  The message length is incorrect.
*F:Hamming code : Faulty check code.
*F:Time tolerance : The measured character length is beyond the tolerance set SIMO.
*F:Spike : The received sign is smaller than 20% of the short pulse.

 