2.1 LIAN 98 Protocol Router |
|
|
|
Protocol 60870-5-104 ( TCP / IP ) over LAN is increasingly used for the connection to control centers.
Companies already running IEC 60870-5-101 substations can convert the serial protocol IEC 101 into the network
protocol IEC 60870-5-104 with LIAN 98. In this way it is possible to maintain the complete telecontrol equipment. |
![]() |
|
When during commissioning not all system components ( e.g. the IEC104 client or a IEC101 substation ) are
available it is of course possible to simulate temporarily the missing components for the integration test with LIAN 98. |
|
|
![]() |
| aktivate router |
yes / no |
| Telegram format |
With this parameter the telegram format of the connected substation is selected ( at the moment only IEC 60870-5-101 ). |
|
Insert routing addresses Number of adresses delete insert |
All connected substations which should be taken into account from the IEC104 router are to be entered into
the station list. |
|
|
![]() |
| End of initialization |
yes / no |
| Use system time |
yes / no |
| Send ACTCON respond |
yes / no |
| Send ACTTERM respond |
yes / no |
| Send ACTCON respond on test command |
yes / no |
|
|
![]() |
| Activate router |
yes / no |
| Telegram format |
With this parameter the telegram format of the connected client/ master is selected. ( at the moment only IEC 60870-5-104 ). |
| Route ACTCON respond |
yes / no |
| Route ACTTERM respond |
yes / no |
|
|
![]() |
| Activate time synchronization |
yes / no |
| Use system time |
yes / no |
| Activate general interrogation |
yes / no |
| Send execute command |
yes / no |
|
Wuerzburger Ring 39, D 91056 Erlangen |
LIAN 98 Protocol Router, Simulator and Analyzer © Copyright 2001, 2006 by MAYOR GmbH. All Rights reserved. |